15 

 

 

 

  Attention 



Take care that the naming convention is IEC 61131-3 compatible (no special characters

...); otherwise the button Finish will not be available in the dialog. See also: 

Variable 

names

 (on page 19) 

 

  Info 



The variables declared in zenon are always entered in the Global area of the variable list in 

straton. 

 

 



3.5.3

 

Using zenon variables in straton 

It is very easy to further process variables from PLC systems such as e.g. Siemens S7 or Beckhoff 

TwinCAT in straton, variables which were read in by the according zenon drivers in zenon. 

One possibility to realize this functionality is the allocations (see Allocations). The variable from the PLC 

(e.g. S7 ) is linked to a straton variable with an allocation. In this case only a unidirectional 

communication is possible. 

PLC variables (e.g. from a S7) can be exchanged between zenon and straton via a shared memory 

connection bidirectionally (!), easier and quicker . In the properties of the PLC variable the flag 

Externally visible has to be set to make the variable available in the straton Workbench. 



16 

 

 

 

 



 

As soon as this flag is set, the variable is displayed in the variable list of the straton Workbench. 




17 

 

 

 

  Attention 



Regard interactions with property Hysteresis:  

If a Hysteresis was configured for the zenon variable, the value in straton does not match 

the value in the PLC. It is also possible that it does not match the value in zenon:  

 



If the value changes in the PLC and stays within the configured hysteresis, it is not communicated 

to the zenon Runtime and therefore also not to straton. 

 

If the value is changed by the user in zenon (e.g. via a function) and the value stays within the 



configured hysteresis, the value remains the same in zenon and in straton but it changes in the 

PLC.  


 

If the value is changed in straton and stays within the hysteresis, the value in the PLC and in 



stratonchanges. It remains however the same in zenon.  

If in this situation the value changes in the PLC and stays within the hysteresis, three different 

values exist.  

one in the PLC, one in zenon and one in straton. 

 

Such a variable is especially marked in straton, as it cannot be changed in straton. Changing the variable 



here would lead to problems, as the source of the variable is the PLC programming environment in the 

external PLC (e.g. S7). 

  Attention 

Be careful with the variable name! The name of the variable from an external PLC has to 

be IEC 61131-3 compatible. Also see 

Variable names

 (on page 19). 



18 

 

 

 

In straton a so-called I/O driver - shared memory driver - must be loaded in order to make the 



communication for such variable possible in the Runtime. 

In order to do this open the fieldbus configuration in the straton Workbench with 



File -> Open... -> 

Fieldbus configuration

The following dialog opens with the menu 



Insert -> Insert configuration...

  



Here select the configuration 

straton to zenon-RT

 connection. So this configuration is inserted in 

the tree of the fieldbus configuration: 

 

Now it is guaranteed that the externally visible variables from zenon communicate with straton. 



  Info 

Please be aware, that such a connection only works locally on a PC or a CE device. Here it 

is not possible to communicate with a straton Runtime on another device. 

With the help of the zenrt driver complex variables (arrays and structure variables )are resolved into a 

flat structure. The values of variables with the same name in straton and zenon are exchanged via the 

shared memory driver. 




19 

 

 

 

  Info 



The functions for checking the status of a variable and for setting Dirty are not supported 

at the moment. 

The status information (time stamp and status bits) are not supported for complex data 

types. 

If you marked an element of an array or a structure variable as externally visible, a simple variable with 

the same name is created in the straton Workbench. If you marked the array or the structure variable 

itself as externally visible, this complex variable is created in the workbench. 

  Info 

If you mark an array or a structure variable as externally visible, the individual elements are 

not created in the Workbench anymore. 

You can create variables in the workbench, which contain characters '.' or '[]' in their 

name. Therefore you can create variables which have the same name as variables which 

derive from an array or a structure variable. In this case the communication with the zenrt 

driver is not possible as no distinct allocation can be made. 

 

 



3.5.4

 

Variable names 

In straton variable names must be in accordance with the IEC 61131-3 regulations. The correctness of 

the entry is checked by  zenon as well as by straton (communication take place using the STRATON32 

driver). 

For variables of other drivers (e.g. S7 TCO/IP driver), the engineer has to check that the variable name 

fulfills the regulations of the IEC 61131-3 (communication takes place using shared memory). 

_XYZ 


__XYZ 

Twice with Underscore 

xy_z 

xy__z 


Twice with Underscore 