Depending on the current status, the user interface displays different states (



running



step 



mode

,

break point(s)



stopped

). 


 

A bar chart shows the PLC load.  

In addition to information about the status of the straton project running, the following actions can be 

executed in the straton Runtime user interface: 

 

Slider Allowed maximum of the PLC resources:set allowed maximum 



 

Settings... (on page 27) button: Makes configuration possible via three tabs 

 

General settings



 (on page 27) 

 



Redundancy

 (on page 29) 

 

Advanced users



 (on page 30) 

 



Start/Stop button: opens the dialog to start Runtime or stops Runtime 

 



Messages (on page 32) button: opens and closes the message window  

 

5.1.1

 

Slider Allowed maximum 

The slider Allowed maximum is used to guarantee other applications which run on the same device - 

such as zenon - system resources. 

With this slider the maximal allowed execution time related to the cycle time can be set. If with a set 

cycle time of 10 ms the slider is set to 50% the PLC cycle may take a maximum of 5ms. If the PLC cycle 

takes longer that 5 ms, the remaining calculation is done in the next cycle. So one cycle has to be 

omitted from the PLC. This results in a cycle overflow. 

The slider can be set between 10% and 100% steplessly.  




27 

 

 

 

The bar graph (PLC load) shows, how high the PLC load is in relation to the setting of the slider. From 



this you can conclude how to set the slider for an optimal tuning. 

PLC load high (Slider between 50 and 100%): Set slider towards 100% or increase cycle time. 

 

5.1.2

 

Settings 

The settings make it possible to configure the straton Runtime with the help of three tabs: 

 



General settings 

 



Redundancy  

 



Advanced users 

 

General 

In the tab General the different parameter of the straton Runtime can be changed: 

Communication 

 

Port (Main):  

IP port of the straton Runtime for the cyclic data transfer (e.g. straton 

Workbench). 



Port (Binding):  

IP port of the straton Runtime for the on change data transfer (e.g. 

CA_PRODUCTNAME

 Workbench or binding). 



Run-up 

 

No start. Open this box:  

When the straton Runtime is started, first this box is opened. 

Cold start:  

Initialized run-up. Also retain variables are started initialized. 



Cold start (loading of RETAIN 

variables):  

Initialized run-up with current values of the retain variables. 



Warm start:  

Restart with all variable values from the last stop. 



Delay [s] 

Delays the start by the set number of seconds. 




28 

 

 

 

Default: 0



 

Storage path RETAIN data 

Here the file with the retain variables is stored. The default setting depends 

on whether the straton Runtime is started.  

Real-time priority 

Sets the straton Runtime process to the windows priority 



Realtime

. If the 

flag is not set, it means priority 

Normal



Start in step mode 

Starts the straton Runtime and immediately stops it in debug mode. 

Write messages to 

STRATONRTLOG.TXT 

Error messages which were generated by the straton Runtime are saved in 

this file. 

Writing log files can influence the PLC cycle! 

 

  Info 


If the straton Runtime has been started with the zenon Runtime or with the straton 

Runtime Manager, changes done in this user interface are not effective after a restart of 

the straton Runtime. Please make the changes as usual in the straton project properties of 

the zenon Editors or in the straton Runtime Manager. 

In such cases the dialog helps to determine which parameters were forwarded to the 

straton Runtime. 

 

The changes to the settings which were done in this dialog are only effective if the straton 

Runtime is started directly (e.g. using the Windows Explorer). 


29 

 

 

 

 



 

Redundancy 

In tab Redundancy you can see the redundancy settings for the straton Runtime. 

 

You can check or enter the following entries: 



Activate redundancy 

Runtime runs in redundancy mode 



Server port: 

Port for replication connection 



Server Time-out [ms] 

Time-out in order to determine if the passive client is 

available. After the time-out expires, the replication is 

stopped. 



Client Time-out [ms] 

Time-out in order to determine that the active server is no 

longer available. After the time-out expires, the passive 

client becomes the active server. 



Partner address: 

IP address of the redundancy partner. 

 