35 

 

 

 



 

Change the Start type (Runtime) as you wish. The properties of Start type are described 

in the embedded help in zenon. 

You can use the straton Runtime Manger to start the straton Runtime manually. You will find the 

straton Runtime Manager in the folder COPA-DATA in the Windows ®  start menu. The straton 

Runtime manager is used to start straton Runtime instances on a PC. You can for example chose 



hard 

real time

 here in order to start the straton real time version (straton RTK) or to start a straton 

Runtime instance during the booting of the system ("Auto start"). 

 

You receive accurate information about the individual elements of the straton Runtime manager by 



moving the mouse pointer over them. Then the corresponding help is displayed in the embedded help. 

You receive the complete help about this application by clicking ? in the menu bar. 

The straton Runtime can be started in a DOS Shell or something similar (.bat file). For the command the 

following is true: 

 

all commands must be entered in capitals 




36 

 

 

 



 

the following signs are allowed:  

-  

/   


no sign 

The following handover parameters are available: 



PORT=

 

Communication port. 



Without parameters: 1200

 

PORTTRACE=

 

Event server point, Binding port.  



Without parameters: PORT+7800

 

PATH=

 

Storage area of the straton application code. 



Without parameters: straton Runtime directory

 

ZENPATH=


 

zenon path (without meaning) 



ZENPROJECT=

 

zenon project name (without meaning) 



DONTHIDE

 

Do not hide the Runtime after the start (it is the only parameter without '=') 



STEP=<0|1>

 

Without parameters: no stepping mode.  



0: no stepping mode  

1: Start in stepping mode 



START=<0|1|2|3>

 

Without parameters: Warm start  



0: Display setup dialog  

1: Cold start  

2: Warm start  

3: Hot start 



LOWPRIORITY=<0|1>

 

Without parameters: low priority  



0: low priority  

1: Windows real time priority 



WRITELOG=<0|1>

 

Without parameters: Create log  



0: Do not create log  

1: Create log  

The log-file is created in the PATH directory as STRATONRTLOG.TXT. 



37 

 

 

 

REMPATH=


 

Path for remanent data. 

Without parameters: PATH directory 

DELAY= 

Start delay in [s]: Delayed start of the straton Runtime. 

Without parameters: 0 

MAXUTILPRCT=

r> 


Position of the slider for maximum PLC workload in %. 

Without parameters: 100 

Settings equal to the settings under Settings/Advanced for the event server. 

QSSYSTEM= 

Size of system queue.  

Without parameters: 1024

 

QSALARM= 



Size of alarm queue.  

Without parameters: 0

 

QSEVENT= 



Size of event queue.  

Without parameters: 8192

 

QSINFO= 



Size of info queue.  

Without parameters: 32768

 

NBEVENT= 



Maximum number of recordable events.  

Without parameters: 1024

 

EVENTCON= 



Number of possible event connections.  

Without parameters: 256 




38 

 

 

 

REDENABLE=<0,1> 



Redundancy on/off.  

Without parameters: 0

 

REDADDR= 



Redundancy partner address. 

REDPORT= 

Redundancy port for replication. 

REDCLITIMEOUT= 

Redundancy client time out [ms]; time out which is used to determine when a 

passive client becomes an active server. 

Without parameters: 1000

 

REDSRVTIMEOUT= 



Redundancy server time out [ms]; time out which is used to determine when the 

replication is stopped. 

Without parameters: 1000

 

REDZENON=<0,1> 



If set to 1, the partner address is read from PROJECT.INI. Without 

parameters: 0 

 

 

 



The straton Runtime cycle consists of: 

 



Calc. time: Time for data exchange, calculation, save calculated values, read and write modified 

values, idle time. 

 

Cycle time: Complete cycle time determined by system latency. 



 

System latency: Response time of the system.  




39 

 

 

 

These values can be displayed in the straton user interface. Use the shortcut 



Alt+S

 or 


Shift+Alt+A

 



Binding exchange 

Reading of the Binding values which are published in the network and which were 

configured by the application (if they were configured). 

I/O exchange 

Data exchange between the I/O drivers (except Modbus slave/server) and the I/O 

boards (if they were configured). 

Application execution 

Execution of the programs. 



Digital sampling trace 

Execution of the digital sampling (if it was configured). 



Events 

Sending of the events (Binding or straton32.exe driver of zenon) (if they were 

configured). 

Forced values 

Reading of the forced values of zenon from the straton Workbench (online 

debugging) and data exchange of the Modbus slave/server (if they were configured). 

Sleep 

Wait the remaining time until the cycle time is over. 

When cycle setting is 

As fast as possible (free run)

, the time is 

always 1 ms.  

The Sleep time is used in order to execute tasks of the operation system and of other 