-12-
For example if the brightness decreases, if the experimenter touches the ground wire of the
transmitter, he is now the receiver.
2.8 Conclusion
There is a feedback from the receiver to the transmitter, as can be observed here. With the
transmission of radio waves no such feedback should be determined. Only with resonance
between transmitter and receiver, scalar waves are developed. If the transmitter is unplugged
or the generator frequency changes and leaves so the conditions of resonance, no more energy
is transferred.
2.9 Consequences
Numerous interhuman effects are based on the principle shown in the feedback from the
receiver to the transmitter. They are in this way for the first time physically modelled. At the
same time it becomes clear that the as esoteric classified coherences are nothing else than scalar
wave effects. These effects are wrongfully designated as para-science, because scalar waves
are still unknown to the scientific world. The feedback shown in the experiment proves the
existence of scalar waves!
2.10 Utilities:
Demo kit like in experiment 1.
Using the experimentation kit: pancake coil "A" with middle wire length
- 1 3 -
3rd experiment, subject:
Proof of free energy
3.1
Experimentator: Prof.
Dr.-Ing. Konstantin Meyl
3.2
Place and date:
D-78112 St. Georgen, 21st of June 2000
3.3
To the status of physics of electromagnetic waves (according to Heinrich Hertz)
It is a physical law, after which the field strength decreases with the square of the distance. As
consequence of the law received power is generally smaller than the transmitted. The field
strength continues to decrease quadratically with the distance.
3.4 Expectation according to the scalar wave theory by Konstantin Meyl
The transmission with scalar waves has no power attrition during transmission (quod vide 1st
experiment). The dielectric between the two spherical electrodes is open and therefore able to
interrelate with scalar wave fields from the environment. If such fields with appropriate
frequency and phase position are present, efficiencies from over 100 % are not to be excluded,
even expectable. Finally, it concerns an open system!
3.5 Experimental setup and carrying out the experiment
The transmission circuit is adjusted as described in experiment 2. The LED's at the transmitter
coil are to be out, while at the receiving coil they have to shine. Further look first for the
resonant frequency please (receivers shines) and then the amplitude has to be accordingly
reduced. Subsequently, with the frequency controller, check again whether it is the correct
point. There is the possibility that the receiver lamps light up at several frequency values, but
only at the correct value the feedback to the transmitter is so strong that the transmitter lamps
fade out completely.
3.6 Interpretation of the experimental results
Both coils should be identical (same numbers of turns, same wire length, same couple coil).
Thus makes sure that the inductively coupled voltage should be larger than the receiptable
under normal conditions. As a matter of fact it is vice versa. On the receiver side values over
the threshold voltage of the LED (2 V) are reached, while on the transmitter side they are not,
because the LED's on the receiver side shine, whether on the transmitter side they do not. The
load by the LED's is identical in both cases, so that the higher voltage leads compellingly to a
higher current and a higher power. That is, it will more power be received than the transmitter
delivers.
-14-
3.7 High frequency measurements
If the appropriate measuring technique is available, the into the transmission coil fed high
frequency power and the received high frequency power can be measured directly. In addition
a short laboratory cable replaces the shorting plug between waveform generator and the
pancake coil and the current signal is measured with current measuring pliers (for high
frequency measurements). The jumper is brought in central position. Thus the connector
sockets on the left side are activated, where the voltage measurement can take place. Due to
the fact that between current and voltage a phase angle arises, the instantaneous values must be
multiplied with one another (the Scope must support this computation!). This results in a
likewise sinusoidal output curve with double frequency, whose average value can be consulted
as measure for the fed power.
The high frequency measurement on the receiver side takes place completely similarly. The
jumper is put in central position and the voltage is measured. A resistor of 100 ohms is
recommended as load. With the current-measuring pliers the current flowing through the load
resistor is measured. By optimal impedance matching of the load resistance and with
appropriate reduction of the amplitude the efficiency can be increased still further.
3.8 Interpretation of the high frequency measurements
Efficiencies of approximate 500% are measured. An appropriate measurement with a 200 MHz
power measuring device is printed in the 2nd book from the book series "electromagnetic
environmental compatibility" in chapter 19.11. A control survey took place at the technical
university of Clausthal at the 6th of July 2000. In the Institut for electrical engineering an
efficiency was measured with two Tektronix measuring devices, which averages 1000%. For
the large astonishment of the research workers, the received Power at the middle pancake coil
of the experimentation kit was ten times the power, which was transmitted.
3.9 Circuit analyzer measurements
Not each Institute has the necessary equipment, in order to be able to make high frequency
power measurements. That applies especially to private researchers and schools. For this
group, the third jumper position on the coil plates was designed (DC load). In this position the
high frequency signal is applied to a bridge rectifier, and a condenser is loaded with the
rectified voltage. On the right side of the plate are two sockets, at which DC voltage is
impressed. It can be assumed that nearly everyone has a simple multimeter, which indicates the
voltage level in DC position. The load resistor of 100 ohms is already on the plate, so that the
converted power U
2
/100 ohm can be made directly out off the voltage measurement.