35
Change the Start type (Runtime) as you wish. The properties of Start type are described
in the embedded help in zenon.
You can use the straton Runtime Manger to start the straton Runtime manually. You will find the
straton Runtime Manager in the folder COPA-DATA in the Windows ® start menu. The straton
Runtime manager is used to start straton Runtime instances on a PC. You can for example chose
hard
real time
here in order to start the straton real time version (straton RTK) or to start a straton
Runtime instance during the booting of the system ("Auto start").
You receive accurate information about the individual elements of the straton Runtime manager by
moving the mouse pointer over them. Then the corresponding help is displayed in the embedded help.
You receive the complete help about this application by clicking ? in the menu bar.
The straton Runtime can be started in a DOS Shell or something similar (.bat file). For the command the
following is true:
all commands must be entered in capitals
36
the following signs are allowed:
-
/
no sign
The following handover parameters are available:
PORT=
Communication port.
Without parameters: 1200
PORTTRACE=
Event server point, Binding port.
Without parameters: PORT+7800
PATH=
Storage area of the straton application code.
Without parameters: straton Runtime directory
ZENPATH=
zenon path (without meaning)
ZENPROJECT=
zenon project name (without meaning)
DONTHIDE
Do not hide the Runtime after the start (it is the only parameter without '=')
STEP=<0|1>
Without parameters: no stepping mode.
0: no stepping mode
1: Start in stepping mode
START=<0|1|2|3>
Without parameters: Warm start
0: Display setup dialog
1: Cold start
2: Warm start
3: Hot start
LOWPRIORITY=<0|1>
Without parameters: low priority
0: low priority
1: Windows real time priority
WRITELOG=<0|1>
Without parameters: Create log
0: Do not create log
1: Create log
The log-file is created in the PATH directory as STRATONRTLOG.TXT.
37
REMPATH=
Path for remanent data.
Without parameters: PATH directory
DELAY=
Start delay in [s]: Delayed start of the straton Runtime.
Without parameters: 0
MAXUTILPRCT=
r>
Position of the slider for maximum PLC workload in %.
Without parameters: 100
Settings equal to the settings under Settings/Advanced for the event server.
QSSYSTEM=
Size of system queue.
Without parameters: 1024
QSALARM=
Size of alarm queue.
Without parameters: 0
QSEVENT=
Size of event queue.
Without parameters: 8192
QSINFO=
Size of info queue.
Without parameters: 32768
NBEVENT=
Maximum number of recordable events.
Without parameters: 1024
EVENTCON=
Number of possible event connections.
Without parameters: 256
38
REDENABLE=<0,1>
Redundancy on/off.
Without parameters: 0
REDADDR=
Redundancy partner address.
REDPORT=
Redundancy port for replication.
REDCLITIMEOUT=
Redundancy client time out [ms]; time out which is used to determine when a
passive client becomes an active server.
Without parameters: 1000
REDSRVTIMEOUT=
Redundancy server time out [ms]; time out which is used to determine when the
replication is stopped.
Without parameters: 1000
REDZENON=<0,1>
If set to 1, the partner address is read from PROJECT.INI. Without
parameters: 0
The straton Runtime cycle consists of:
Calc. time: Time for data exchange, calculation, save calculated values, read and write modified
values, idle time.
Cycle time: Complete cycle time determined by system latency.
System latency: Response time of the system.
39
These values can be displayed in the straton user interface. Use the shortcut
Alt+S
or
Shift+Alt+A
.
Binding exchange
Reading of the Binding values which are published in the network and which were
configured by the application (if they were configured).
I/O exchange
Data exchange between the I/O drivers (except Modbus slave/server) and the I/O
boards (if they were configured).
Application execution
Execution of the programs.
Digital sampling trace
Execution of the digital sampling (if it was configured).
Events
Sending of the events (Binding or straton32.exe driver of zenon) (if they were
configured).
Forced values
Reading of the forced values of zenon from the straton Workbench (online
debugging) and data exchange of the Modbus slave/server (if they were configured).
Sleep
Wait the remaining time until the cycle time is over.
When cycle setting is
As fast as possible (free run)
, the time is
always 1 ms.
The Sleep time is used in order to execute tasks of the operation system and of other