Chemical Handling and Storage 0

Standard Operating Procedure for Chemical Handling and Storage 
EHS-00005 R12

Printed copies are considered uncontrolled. Verify revision prior to use.


 
DCN1216 
CNSE Confidential
Page 17 of 43 
10.7.4 
Unopened containers should be dated upon receipt (DD/MM/YYYY) and if 
not used disposed of after 12 months.
11. 
PYROPHORIC CHEMICALS 
11.1 
Storage
11.1.1 
Pyrophoric liquids in quantities greater than 0.4 gallons shall be stored in 
an approved flammable storage cabinet or exhausted enclosure that is 
constructed of at least #18 gauge steel and is equipped with a highly 
sensitive smoke detection device. 
11.1.2 
If used, the highly sensitive smoke detector shall be tied into the fire alarm 
control panel which will page the ERT directly. 
11.1.3 
Accept delivery from the shipping department and transfer immediately to 
the storage location. Unpack vessel from the shipping packaging. 
11.1.1 
Upon receipt of a pyrophoric liquid the ampoule and inner metal container 
should be checked that it is labeled with the name and hazard 
classification. If such a label is not present then a HMIS or NFPA label 
must be attached to identify the name and hazards associated with the 
chemical. 
11.1.2 
Also upon receipt the receiver must attach a ‘status tag’ to the outside of 
the ampoule and inner metal container to identify its current state of ‘full, 
in-
use or empty’. 
11.1.3 
Place the container in the designated flammable storage cabinet. 
11.1.4 
In the case of a spill or emergency contact the emergency response team 
at 78600 or (518) 437-8600 immediately. Those handling emergencies 
associated with this material should follow the guidelines, equipment and 
PPE specified in the ERT Standard Operating Procedure. 
11.1.5 
Emergency response PPE and spill equipment shall be located near the 
storage cabinet to allow for immediate emergency response. 
11.2 
Delivery
11.2.1 
Pyrophoric liquids shall be transported on a cart with the ampoule inside a 
metal container/housing.
11.2.2 
Pyrophoric liquids can only be delivered to the NFN chemical pass-
through between the hours of Monday-Friday 9:00am-3:00pm and handed 
off directly to the person using them. Once received, this material shall be 
transported directly to the cabinet and loaded immediately.