Standard Operating Procedure for Chemical Handling and Storage
EHS-00005 R12
Printed copies are considered uncontrolled. Verify revision prior to use.
DCN1216
CNSE Confidential
Page 3 of 43
agents which act on the hematopoietic system, and agents which damage
the lungs, skin, eyes, or mucous membranes.
3.4
Control Area:
Spaces within a building which are
enclosed and bounded
by exterior walls, fire walls, fire barriers and roofs, or a combination
thereof, where quantities of hazardous materials not exceeding the
maximum allowable quantities per
control area are stored, dispensed,
used or handled.
3.5
Combustible Liquid.
A liquid having a closed cup flash point at or above
100
o
F (38
o
C). Combustible liquids shall be subdivided as follows:
3.5.1
Class II. Liquids having a closed cup flash point at or above 100
o
F (38
o
C)
and below 140
o
F (60
o
C).
3.5.2
Class IIIA. Liquids having a closed cup flash point at or above 140
o
F
(60
o
C) and below 200
o
F (93
o
C).
3.5.3
Class IIIB. Liquids having a closed cup flash point at or above 200
o
F
(93
o
C).
3.6