Standard Operating Procedure for Chemical Handling and Storage



Yüklə 451,69 Kb.
Pdf görüntüsü
səhifə7/39
tarix30.12.2023
ölçüsü451,69 Kb.
#164761
1   2   3   4   5   6   7   8   9   10   ...   39
Chemical Handling and Storage 0

6. 
BULK STORAGE AREAS 
6.1 
Areas and rooms in which chemicals are stored, in excess of the short-
term, in-use quantities, shall be designed and maintained in accordance 
with New York State Building and Fire Codes, National Fire Protection 
Association Codes and federal Occupational Health and Safety 
Administration (OSHA) Regulations. The Facilities Operations Group is 
responsible for the design construction and general maintenance of these 
areas. The Cleanroom / Laboratory Manager (and Gas & Chemical 
handling group) are responsible for the safe operation of these areas. The 
EHS Department shall be contacted for interpretation and application of 
the appropriate codes. 


Standard Operating Procedure for Chemical Handling and Storage 
EHS-00005 R12

Printed copies are considered uncontrolled. Verify revision prior to use.


 
DCN1216 
CNSE Confidential
Page 7 of 43 
6.2 
General Requirements for Bulk Storage Areas
6.2.1 
When less than 300 square feet of storage: the area must consist of 
minimum one-hour fire resistive construction. 
6.2.2 
When greater than 300 square feet of storage: the area must consist of 
minimum two-hour fire resistive construction. 
6.2.3 
Floors shall be non-combustible and liquid tight. 
6.2.4 
Spill containment shall be provided through the use of sills, sumps and/or 
drains. 
6.2.5 
Exhaust ventilation at the rate of one cubic foot per minute per square foot 
of floor area, or six air changes per hour, whichever is greater, and 
arranged such that exhaust is taken within 12 inches of the floor. 
6.2.6 
Exhaust ventilation shall not be re-circulated within the room or building. 
6.2.7 
Electrical wiring and equipment shall be installed in accordance with the 
Electric Code. In areas where flammables are stored, electrical equipment 
and wiring shall be approved for Class I, Division 1, hazardous locations. 
6.2.8 
When there is the possibility of an explosive environment, storage rooms 
shall be located on the outer perimeter of the building and provided with 
explosion venting. 
6.2.9 
Non-compatible chemicals shall be separated by a noncombustible solid 