Standard Operating Procedure for Chemical Handling and Storage


partition extending 18 inches above and to the sides of the stored



Yüklə 451,69 Kb.
Pdf görüntüsü
səhifə8/39
tarix30.12.2023
ölçüsü451,69 Kb.
#164761
1   ...   4   5   6   7   8   9   10   11   ...   39
Chemical Handling and Storage 0


partition extending 18 inches above and to the sides of the stored 
material, or separated by a distance of not less than 20 feet, or stored in 
approved hazardous material storage cabinets (see Appendix A - Figure 1 
for minimum material separation). In Figure 1, the Toxic heading 
references gases only. For solids and liquids which are labeled as poisons 
or toxics, secondary hazard labels (for example, Hydrogen Fluoride 
– 
Corrosive (Acid) / Poison) shall be referred to in order to determine 
compatibility. 
6.2.10 
Categories requiring separation are flammables, acids, bases and 
oxidizers. See Appendix B - Figure 2 for a listing of common chemicals 
utilized in research laboratories with examples of incompatibles.
6.2.11 
Self-contained breathing apparatus (SCBA), minimum of two, shall be 
installed in an immediately accessible location outside of the room. For 
responding to the Central Utility building (CUB) bulk chemical storage 
areas, the nearest SCBAs are just inside the NanoFab South (NFS) 
delivery door, outside the Emergency Response Team (ERT) supply 
room. 


Standard Operating Procedure for Chemical Handling and Storage 
EHS-00005 R12

Printed copies are considered uncontrolled. Verify revision prior to use.


 
DCN1216 
CNSE Confidential
Page 8 of 43 
6.2.12 
Emergency eyewash and showers shall be readily available, preferably 
installed such that the maximum travel distance from any point in the room 
to the shower is 25 feet or less or 10 seconds or less. 
6.2.13 
Emergency communication shall be provided and monitored at a remote 
location at all times when someone may be working in the area alone.
6.2.14 
Any chemical or gas that has been identified as expired (i.e. beyond 
manufacturers expiration date on containers) or “out of specification” 
material that cannot be used in the laboratory or cleanroom tools must be 
"RED TAGGED" by the shipping and receiving department or the gas and 
chemical handling firm’s personnel upon delivery, or the responsible 
chemical user if discovered during storage or use. The material container 
must be tagged on all sides (cylinders require only 1 tag). 
If the “out of 
specification” material is in a laboratory or in a cleanroom, it should be 
either stored in an appropriate cabinet for return to the supplier or moved 
to the chemical storage rooms by the gas and chemical handling firm. 
Expired material if determined to be unusable should be sent for disposal 
as a waste chemical through the gas and chemical handlers.