30 

 

 

 

  Info 



You can fing details on configurating the redundancy of straton and zenon in chapter 

Redundancy straton and zenon

 (on page 60).  

 

 



Advanced users 

In the tab Advanced you carry out settings for the on change communication with external 

applications (Binding, zenon driver, ...). 

 

The following settings are available: 



System 

Max. length of the system queue. In this queue e.g. 

overflows of the event queue are buffered. 

1024 ... 65520  

Default: 1024

 

Alarms 

Length of the alarm queue (not used at the moment) 

0 ... 65520  

Default: 0

 



31 

 

 

 

max. connections 

Number of possible connections (cannot be changed) 

4 ... 65535  

Default: 256

 

Events 

Length of the event queue: 

In this queue the events of the straton Runtime event severs 

are written. From there they are sent via TCP. 

If this queue overflows, the overflow messages are written 

in the system queue.

 

0 ... 65535  



Default: 8192

 

Messages 

Length of the info queue. In this queue the messages to the 

straton Workbench are buffered. 

1024 ... 65520  

Default: 32768

 

max. puffer 

Buffer size of the events per cycle. This parameter defines 

how much many variables are handled by the event server 

per cycle. 

128 ... 65535  

Default: 1024

 

Reset  

Restores the default settings 

 

 

  Info 



If in large projects more than 1024 variables are transferred between straton and zenon 

with the straton32.exe driver, the parameter Max. buffer must be increased 

accordingly. An easy method to find out the number of Max. buffer is the value for the 

compiled I/Os in the output window of straton compilers. See illustration below. 

 

 




32 

 

 

 

5.1.3

 

Messages 

Runtime messages can be displayed in the straton Runtime user interface. Click on the Messages>> 

button to activate the view. The message display opens. Click on the Messages<< button to close the 

message display.  

 

For actions in the message display, click in the message display with the left or right mouse button. You 



obtain a context menu: 

Display time stamp of messages 

Adds a time stamp to each message. 



Copy messages to the clipboard 

Copies selected entries to the clipboard. 



Delete all messages 

Deletes all messages from the message window.  

You administer the settings for straton logging and the drivers with the diagnosis viewer.  In doing so, 

each straton Runtime and each bus driver receives their own connection to the diagnosis server as a 

diagnosis client. This does not include obsolete drivers, for example those from a third-party 

manufacturer. 

 



33 

 

 

 

 



The straton Runtime is automatically licenced with the zenon serial number. During the installation enter 

the serial number and the activation number in the according dialog. If no licence number is available, 

click on Demo Version (on page 34). 

For an autarkic installation (straton runs on a PC without the zenon Runtime) you can again enter the 

serial number and the activation number directly in the installation dialog. 

You also can do the licensing later with the Licence order. Open the license order in the Windows start 

menu under 

Programs -> COPA-DATA -> Licensing

. For later licensing the serial 

number and the activation number are entered in this dialog. The 

procedure is finished with OK.

 

For soft-licensing the so-called licence number must be read from the hardware configuration of your 



PC. Click the button for soft licensing and follow the requests in the following dialogs. 

In the zenon Editor you can open the dialog for licensing using 



File -> Standard configuration -> License 

product...

. You can enter the serial number and the activation key here. 

Open the user interface of the straton Runtime by clicking on the straton Runtime icon in the system 

tray. Then click on the top left corner an select About STRATONRT.... A window appears with 

information about version and license of the straton Runtime. 

 

 




34 

 

 

 

5.2.1

 

Demo mode 

straton Runtime starts in Demo Mode if you enter a false (or no) serial number or a false (or no) 

activation key or if no dongel is connected. The Demo Mode stops the straton Runtime after 15 minutes. 

With a special demo serial number the straton Runtime runs continuously for 30 days. After these 30 

days then the maximal time of the straton Runtime is again 15 minutes. 

You did not buy the straton Runtime license but you own a valid zenon Runtime license. Then a mini 

version of the straton Runtime is licensed automatically. With the mini version up to eight TAGs 

(=variables) can be used by straton via input/output mechanisms. TAGs are variables of field bus drivers 

and variables with profiles (e.g. B&B profile straton). 

Calculation example: 

 

four variables for the communication  straton <= > zenon 



 

four variables for the communication  straton <= > Profibus 



 

This equals the maximum number of eight TAGs (4 + 4 = 8). 



 

 

The straton Runtime supports multi-instances and therefore needs parameters (transfer parameters), 



when it is started. 

There are three possibilities in order to start the straton Runtime: 

1.

 

with the help of the zenon Runtime 



2.

 

with the help of the straton Runtime Manager 



3.

 

in a DOS Shell/BAT-file 



In order to start the straton Runtime with the zenon Runtime: 

 



Select the straton project in the zenon Editor.  